Place vent support straps along the pipe every 8 feet if it s more than 25 feet long.
How far should a flu be installed above a roof.
When installing a new twinwall flue system if the flue exits the roof within 600mm horizontally from the ridge high point of the roof then the flue must extend a minimum of 600mm above the ridge.
Keep flue pipe as straight as possible for horizontal runs.
Minimum clearance from combustible material.
The minimum clearance may be reduced by 50 percent to 225 mm 9 in if suitable shielding is installed either on the pipe or on the combustible surface.
For gas vents or a type l vent this distance above the roof surface must be at least 2 ft 0 61m.
Install no more than two elbow pipes at 45 degree angles if running the pipe through a chimney stack.
In other words the highest point within a 10 foot circle of the pipe.
Set the collar with the wide flange at the bottom on the surface of the roof.
A flue pipe must never pass through a combustible floor or ceiling or through an attic roof space closet or concealed space.
If the flue exits the roof further down then it must extend high enough to acheive 2 3m of horizontal clearance.
Roof sheathing is attached to the roof framing trusses or rafters and provides the nail base for the other components of the roof system.
Extend the vent pipe at least.
If the pipe is farther than 10 feet from the roof peak it must be 2 feet above the highest point of the roof within 10 feet.
Vent caps larger than 12 must be located at least 2 feet above the highest point and 2 feet higher than any portion of the building within a horizontal distance of 10 feet.
450 mm 18 in.
This specification makes sure steep roof slopes are cleared.
The top of the chimney should be at least 3 ft 0 92 m above the roof surface.